How to Fix a Faulty Expansion Valve in a Constant Temperature and Humidity Test Chamber

Source:LINPIN Time:2025-04-27 Category:Industry News

A constant temperature and humidity test chamber consists of multiple components, and any malfunction can disrupt testing. Previously, we discussed troubleshooting methods for other issues. Today, we focus on expansion valve failures.

To resolve expansion valve problems, first identify the root cause. Common issues include:

Irregular refrigerant supply (fluctuating flow)
Excessive subcooling or superheating

constant temperature and humidity test chamber
These problems are often related to the thermal bulb, primarily due to two reasons:

1. Broken Capillary Tube in the Thermal Bulb
If the capillary tube is damaged, the refrigerant charge inside leaks, preventing accurate signal transmission to the expansion valve’s actuator.

2. Incorrect Thermal Bulb Installation
Improper positioning during assembly can lead to malfunction.

Solutions
① For a Damaged Capillary Tube
Repair or replace the thermal bulb (requires professional servicing).
② For Incorrect Thermal Bulb Installation
Correct the installation position:
The thermal bulb head should face downward or horizontally.
It must be installed below the valve diaphragm’s upper chamber, close to the evaporator and away from the compressor suction port.
Avoid vertical installation—it should be mounted on the horizontal section of the evaporator’s outlet pipe.
Additional Guidelines:

If the thermal bulb is installed higher than the diaphragm chamber, bend the capillary tube into a U-shape to prevent liquid refrigerant from entering the chamber.
For horizontal pipes with a diameter > 7/8″:
Install the bulb below the pipe’s centerline, at a 45° angle (3 o’clock position).
For pipes < 7/8″:
Install it at the top (1 o’clock position).
Avoid mounting at the bottom—this reduces sensitivity, causing excessive refrigerant flow and unstable supply.
By following these steps, you can effectively troubleshoot and resolve expansion valve issues in your test chamber. Regular maintenance ensures optimal performance and extends equipment lifespan.

News Recommendation
The uniformity of a thermal shock test chamber directly affects the test results, so it is crucial to maintain optimal uniformity.
The cold and hot shock test chamber is an effective device for detecting the performance of electronic components under rapidly changing temperature conditions. Many materials are tested using this equipment. To ensure the accuracy of the test results, it is necessary to clean the test specimens before the test chamber is operated.
Adjusting the wind speed is crucial for dust and sand test chambers, as it directly affects the test results of the specimens. What are the specific requirements for wind speed during the operation of these chambers? Today, let's delve into the details together.
When maintaining cold and hot shock test chambers, paying attention to details is crucial. A minor oversight can significantly impact the effectiveness of the tests. Therefore, it is essential to prioritize the regular maintenance of testing equipment. Today, let's go over a few key aspects of maintaining test chambers.
When test samples are exposed to low temperatures in a thermal shock test chamber, they may suffer certain adverse effects. This is because the physical properties of the materials can change under extreme cold, potentially leading to performance degradation. So, what specific impacts can occur?
Product Recommendation
Telegram WhatsApp Facebook VK LinkedIn
主站蜘蛛池模板: 毕节市| 沁阳市| 安新县| 武山县| 海南省| 瑞金市| 合阳县| 房产| 墨江| 醴陵市| 东平县| 嫩江县| 若羌县| 大方县| 宁陕县| 泰顺县| 措美县| 二手房| 栖霞市| 紫金县| 滦平县| 双鸭山市| 当雄县| 汪清县| 海淀区| 建德市| 舞阳县| 武汉市| 沂水县| 铜陵市| 江都市| 河津市| 体育| 安徽省| 萍乡市| 历史| 溧水县| 自治县| 黔西县| 裕民县| 会东县|